Architecture Paint
FIRE BLOCKING 105 One-hour fire-resistant paint, for steam beam and column
- usage
- One-hour fire-resistant paint for steel beam and column of buildings
This paint has obtained a domestic fire resistant construction certification (1 hour). It is an oil-based foaming fire-resistant paint for intermediate coating that is designed to protect steel structures from fire by demonstrating strong fire-resistant performance with a thin film. It is a highly functional paint that protects people and property by preventing a sudden collapse due to the decrease of strength of a steel structure in case of a fire as the film forms a thick heat insulation layer by rapid foam expansion once it is heated by flames and delays the transfer of heat.
specification
- Paint type
- Acrylic
- Drying time
-
Drying time Category 5℃ 20℃ Set-to-touch 1 hour 30 minutes Dry-hard 24 hours 12 hours Complete drying more than 2 months more than 1 month Over-coat (Min.) 24 hours 12 hours - Thinner
- Thinner for fire-resistant paint
- Specific gravity
- 1.28±0.05
- Theoretical Coverage
- 1.0 ㎡/ℓ/2times (Beam, Column)
- Dilution ratio
- ▷Airless spray (in principle): less than 3% ▷Brush, roller coating possible (depending on the site situation) ▷Tip diameter : 0.025
- Nonvolatile component
- Approx. 68±2%
- Color
- White
- Thickness of dried film
- 650㎛ (Beam, Column)
- Mixing ratio
- One-component
- Gloss
- Matte
PRODUCT PROPERTIES (PHYSICAL PROPERTY DATA)
- Adhesion strength
- More than the standard (ASTM D 4541)
- Gas hazards
- Acceptable (KS F 2271)
how to use
- Surface treatment
- 1. Completely remove mill scale, oil, moisture, sand, dust, and other foreign matter from the surface to be coated.
2. Sufficiently dry the surface to be coated.
3. If an old film exists on the surface to be coated, apply the undercoat recommended by this company after removing the portion with the poor film condition to the greatest extent possible. - Coating method
- 1. Paint suitable for preceding coating
① Architectural specification: KSM-6030 Class 1 alkyd primer
*Note that wrinkles may occur while applying a fire-resistant paint according to the inside drying condition of the alkyd primer.
② Heavy-duty specification: Epoxy paints such as DHDC-0690; Inorganic zinc paints such as DHDC-1800BG
*Mist coating should be done with DHDC-5000HB, which is an epoxy intermediate coat, when DHDC-1800BG is used.
2. Paint suitable for follow-up coating
① Architectural specification: KSM 6020 class 1 (mixed) class 2 (Enamel), FIRE BLOCKING FAST DRYING TOP COAT
② Heavy-duty specification: Urethane top coat, such as ANYTHANE BG, ANYTHANE PLUS 2740
3. Remarks
① The fire-resistant paint is suitable for interior coating without constant exposure to water and dew condensation. However, when inevitably applying outdoors or areas continually exposed to water,consult the technical department of this company.
* Specifications for external exposed areas: Fire-resistant paint → Epoxy-based sealer → Urethane-based topcoat
When applying epoxy paint over fire resistant paint, the color turns brown, but there is no problem with the product.
② Please carry out follow-up coating after 3 days (summer) and 7 days (winter) after the intermediate coating is completed.